PART 63—AUTOMATIC AUXILIARY BOILERS Authority: 46 U.S.C. 3306, 3703; E.O. 12234, 45 FR 58801, 3 CFR, 1980 Comp., p. 277; Department of Homeland Security Delegation No. 00170.1, Revision No. 01.3. Source: CGD 88-057, 55 FR 24238, June 15, 1990, unless otherwise noted. Subpart 63.01—General Provisions § 63.01-1 Purpose. This part specifies the minimum requirements for safety for each automatic auxiliary boiler, including its design, construction, testing, and operation. § 63.01-3 Scope and applicability. (a) This part contains the requirements for automatic auxiliary boilers, including their controls, control system components, electrical devices, safety devices, and accessories. Types of automatic auxiliary boilers which are covered include large and small automatic auxiliary boilers, automatic heating boilers, automatic waste heat boilers, donkey boilers, miniature boilers, electric boilers, fired thermal fluid heaters, automatic incinerators, and electric hot water supply boilers. Automatic auxiliary boilers are classified by their service, control systems, pressure and temperature boundaries, heat input ratings, and firing mediums as follows: (1) Automatic auxiliary boilers listed in table 1 to § 54.01-5 of this subchapter which reference this part for regulation of their automatic controls. (2) Automatic control systems for automatic auxiliary boilers having a heat input rating of less than 12,500,000 Btu/hr. (3.66 megawatts). (3) Electric hot water supply boilers (heaters) containing electric heating elements rated at 600 volts or less. (4) Exhaust gas boilers, and their controls and accessories used to heat water and/or generate steam. (5) Incinerators (and their control systems) used for the generation of steam and/or oxidation of ordinary waste materials and garbage. This part also includes incinerators which serve as automatic auxiliary boilers. (6) Fired thermal fluid heaters and their controls. (b) Automatic boilers having heat input ratings of 12,500,000 Btu/hr. (3.66 megawatts) and above must meet the requirements of part 52 of this subchapter. Their control systems must meet the requirements of part 62 of this subchapter. [CGD 88-057, 55 FR 24238, June 15, 1990, as amended by USCG-2002-13058, 67 FR 61278, Sept. 30, 2002; USCG-2004-18884, 69 FR 58346, Sept. 30, 2004; USCG-2020-0634, 89 FR 50196, June 12, 2024] Subpart 63.05—Reference Specifications § 63.05-1 Incorporation by reference. Certain material is incorporated by reference into this part with the approval of the Director of the Federal Register under 5 U.S.C. 552(a) and 1 CFR part 51. To enforce any edition other than that specified in this section, the Coast Guard must publish a document in the Federal Register [email protected] www.archives.gov/federal-register/cfr/ibr-locations [email protected] (a) American Society of Mechanical Engineers ASME [email protected] www.asme.org (1) ASME CSD-1-2018, Controls and Safety Devices for Automatically Fired Boilers, issued October 12, 2018 (“ASME CSD-1”); IBR approved for §§ 63.10-1(b); 63.15-1(b); 63.20-1. (2) [Reserved] (b) ASTM International [email protected] www.astm.org (1) ASTM F1323-14, Standard Specification for Shipboard Incinerators, approved November 1, 2014 (2001) (“ASTM F1323”); IBR approved for § 63.25-9(a). (2) [Reserved] (c) Canadian Standards Association (CSA), [email protected] https://shop.csa.ca (1) ANSI Z21.22-2015/CSA 4.4-2015, Relief valves for hot water systems, July 2015 (“ANSI Z21.22”); IBR approved for § 63.25-3(a). (2) [Reserved] Note 1 to paragraph ( c CSA material also available from the American National Standards Institute (ANSI), 1899 L Street NW, 11th Floor, Washington, DC 20036; 202-293-8020; [email protected] www.ansi.org (d) International Maritime Organization (IMO), [email protected] www.imo.org (1) Resolution MEPC.76(40), Standard Specification for Shipboard Incinerators, September 25, 1997 (“IMO MEPC.76(40)”); IBR approved for § 63.25-9(a), (d), and (f). (2) Resolution MEPC.244(66), 2014 Standard Specification for Shipboard Incinerators, adopted April 14, 2014 (“IMO MEPC.244(66)”); IBR approved for § 63.25-9(g). (3) The International Convention for the Prevention of Pollution from Ships (MARPOL 73/78), Annexes I, II, III, and V, 1978 (“IMO MARPOL 73/78”); IBR approved for § 63.25-9(c). (e) International Organization for Standardization [email protected] www.iso.org (1) ISO 9096:2017(E), Stationary source emissions—Manual determination of mass concentration of particulate matter, Third Edition, September 1, 2017 (“ISO 9096”); IBR approved for § 63.25-9(f). (2) ISO 10396:2007(E), Stationary source emissions—Sampling for the automated determination of gas emission concentrations for permanently-installed monitoring systems, Second Edition, February 1, 2007 (“ISO 10396”); IBR approved for § 63.25-9(f). (3) ISO 13617:2019(E), Ships and Marine Technology-Shipboard Incinerators—Requirements, Third Edition, August 2019 (“ISO 13617”); IBR approved for § 63.25-9(a). (f) UL Solutions www.ul.com (1) UL 174, Standard for Safety, Household Electric Storage Tank Water Heaters, Eleventh Edition, dated April 29, 2004, including revisions through December 15, 2016 (“UL 174”); IBR approved for § 63.25-3(a) and (j). (2) UL 296, Standard for Safety, Oil Burners, Eleventh Edition, dated February 24, 2017 (“UL 296”); IBR approved for § 63.15-5(c). (3) UL 343, Standard for Safety, Pumps for Oil-Burning Appliances, Ninth Edition, dated December 17, 2008, including revisions through June 12, 2013 (“UL 343”); IBR approved for § 63.15-3(e). (4) UL 1453, Standard for Safety, Electric Booster and Commercial Storage Tank Water Heaters, 6th Edition, dated March 29, 2016, including revisions through March 9, 2017 (“UL 1453”); IBR approved for § 63.25-3(a) and (j). [USCG-2020-0634, 89 FR 50196, June 12, 2024] Subpart 63.10—Miscellaneous Submittals § 63.10-1 Test procedures and certification report. Two copies of the items listed below must be provided, if submitted in printed format, to the Commanding Officer, Marine Safety Center, U.S. Coast Guard, 2703 Martin Luther King Jr. Ave SE, Washington, DC 20593. Alternatively, one copy may be transmitted by email to the Commanding Officer (MSC), at [email protected] www.uscg.mil/HQ/MSC (a) Detailed instructions for operationally testing each automatic auxiliary boiler, its controls, and safety devices. (b) A certification report for each automatic auxiliary boiler that: (1) Meets paragraph CG-510 of ASME CSD-1 (incorporated by reference, see § 63.05-1); and (2) Certifies that each automatic auxiliary boiler, its controls, and safety devices comply with the additional requirements of this part. [USCG-2020-0634, 89 FR 50197, June 12, 2024] Subpart 63.15—General Requirements Source: CGD 88-057, 55 FR 24238, June 15, 1990, as amended by USCG-2020-0634, 89 FR 50197, June 12, 2024, unless otherwise noted. § 63.15-1 General. (a) Each automatic auxiliary boiler must be designed and constructed for its intended service according to the requirements of the parts referenced in table 1 to § 54.01-5 of this subchapter. (b) Controls and safety devices for automatic auxiliary boilers must meet the applicable requirements of ASME CSD-1 (incorporated by reference, see § 63.05-1), except Paragraph CG-310. (c) All devices and components of an automatic auxiliary boiler must satisfactorily operate within the marine environment. The boiler must satisfactorily operate with a momentary roll of 30°, a list of 15°, and a permanent trim of 5° with it installed in a position as specified by the manufacturer. (d) An electrical control used to shut down the automatic auxiliary boiler must be installed in accordance with § 58.01-25 of this subchapter. This device must stop the fuel supply to the fuel burning equipment. (e) Mercury tube actuated controls are prohibited from being installed and used on automatic auxiliary boilers. [CGD 88-057, 55 FR 24238, June 15, 1990, as amended by USCG-2003-16630, 73 FR 65191, Oct. 31, 2008] § 63.15-3 Fuel system. (a) Firing of an automatic auxiliary boiler by natural gas is prohibited unless specifically approved by the Marine Safety Center. (b) Heated heavy fuel oil may be used provided the heaters are equipped with a high temperature limiting device that shuts off the heating source at a temperature below the flashpoint of the oil and is manually reset. When a thermostatically-controlled electric oil heater and a level device is used, it must meet the requirements of subpart 111.85 of this chapter. Note 1 to paragraph ( b An auxiliary boiler may be safely ignited from the cold condition using unheated diesel or light fuel oil and subsequently shifted to heated heavy fuel. (c) The fuel oil service pump and its piping system must be designed in accordance with § 56.50-65 of this subchapter. All materials must meet the requirements of subpart 56.60 of this subchapter. The use of cast iron or malleable iron is prohibited. (d) The fuel oil service system (including the pump) must meet the pressure classification and design criteria found in table 1 to § 56.04-2 of this subchapter. (e) When properly selected for the intended service, fuel pumps meeting the performance and test requirements of UL 343 (incorporated by reference, see § 63.05-1) meet the requirements of this section. [CGD 88-057, 55 FR 24238, June 15, 1990, as amended by USCG-2003-16630, 73 FR 65191, Oct. 31, 2008] § 63.15-5 Strainers. (a) Strainers must be installed in the fuel supply line. Each strainer must be self-cleaning, fitted with a bypass, or be capable of being cleaned without interrupting the fuel oil supply. (b) The strainer must not allow a quantity of air to be trapped inside which would affect the rate of fuel flow to the burner or reduce the effective area of the straining element. (c) The strainer must meet the requirements for strainers found in UL 296 (incorporated by reference, see § 63.05-1) and the requirements for fluid conditioner fittings found in § 56.15-5 of this subchapter. [CGD 88-057, 55 FR 24238, June 15, 1990, as amended by USCG-2003-16630, 73 FR 65191, Oct. 31, 2008] § 63.15-7 Alarms. (a) An audible alarm must automatically sound when a flame safety system shutdown occurs. A visible indicator must indicate that the shutdown was caused by the flame safety system. (b) Means must be provided to silence the audible alarm. The visible indicators must require manual reset. (c) For steam boilers, operation of the lower low water cutoff must automatically sound an audible alarm. A visual indicator must indicate that the shutdown was caused by low water. (d) For a periodically unattended machinery space, the auxiliary boiler trip alarm required by table 1 to § 62.35-50 of this subchapter satisfies the requirements for the audible alarms specified in this section. § 63.15-9 Inspections and tests. All automatic auxiliary boilers must be inspected and tested in accordance with the requirements of part 61 of this subchapter. Subpart 63.20—Additional Control System Requirements Source: CGD 88-057, 55 FR 24238, June 15, 1990, as amended by USCG-2020-0634, 89 FR 50197, June 12, 2024, unless otherwise noted. § 63.20-1 Specific control system requirements. In addition to the requirements found in ASME CSD-1 (incorporated by reference; see § 63.05-1), the following requirements apply for specific control systems: (a) Primary safety control system. (b) Combustion control system. (c) Water level controls and low water cutoff controls. [CGD 88-057, 55 FR 24238, June 15, 1990, as amended by USCG-2003-16630, 73 FR 65191, Oct. 31, 2008] Subpart 63.25—Requirements for Specific Types of Automatic Auxiliary Boilers § 63.25-1 Small automatic auxiliary boilers. Small automatic auxiliary boilers defined as having heat-input ratings of 400,000 Btu/hr. or less (117 kilowatts or less) must also meet the following requirements. (a) Small automatic auxiliary boilers must be equipped with a visual indicator which indicates when the low water cutoff has activated. (b) A prepurge period of a sufficient duration to ensure at least four changes of air in the combustion chamber and stack, but not less than 15 seconds must be provided. Ignition must occur only before or simultaneously with the opening of the fuel oil valve. [CGD 88-057, 55 FR 24238, June 15, 1990, as amended by USCG-2003-16630, 73 FR 65191, Oct. 31, 2008] § 63.25-3 Electric hot water supply boilers. (a) Electric hot water supply boilers that have a capacity not greater than 454 liters (120 U.S. gallons), a heat input rate not greater than 200,000 Btu/hr. (58.6 kilowatts), meet the requirements of UL 174 or UL 1453 (both incorporated by reference, see § 63.05-1), and are protected by the relief device(s) required in § 53.05-2 of this subchapter do not have to meet any other requirements of this section except the periodic testing required by paragraph (j) of this section. Electric hot water supply boilers that meet the requirements of UL 174 may have temperature-pressure relief valves that meet the requirements of ANSI Z21.22 (incorporated by reference, see 4 § 63.05-1) in lieu of subpart 53.05 of this subchapter. (b) Each hot water supply boiler must be constructed in accordance with the applicable requirements of part 52 or part 53 of this subchapter. (c) Branch circuit conductors for hot water supply boilers which have a capacity not greater than 454 liters (120 U.S. gallons) must have a current carrying capacity of not less than 125 percent of the current rating of the appliance. Branch circuit conductors for hot water supply boilers with capacities of more than 454 liters (120 U.S. gallons) must have a current carrying capacity of not less than 100 percent of the current rating of the appliance. Wiring materials and methods must comply with subpart 111.60 of this chapter. A hot water supply boiler having a current rating of more than 48 amperes and employing resistance type heating elements must have the heating elements on subdivided circuits. Each subdivided load, except for an electric hot water supply boiler employing a resistance type immersion electric heating element, must not exceed 48 amperes, and it must be protected at not more than 60 amperes. An electric hot water supply boiler employing a resistance type immersion electric heating element may be subdivided into circuits not exceeding 120 amperes and protected at not more than 150 amperes. Overcurrent protection devices must comply with subpart 111.50 of this chapter. (d) Heating elements must be insulated electrically from the water being heated, guarded against mechanical injury and contact with outside objects, and securely supported. Consideration must be given to sagging, opening, and other adverse conditions of the elements resulting from continuous heating, and flexion of supports and wiring due to alternate heating and cooling. Wrap-around elements must be secured in a manner which prevents loosening. (e) Iron and steel parts must be protected against corrosion by enameling, galvanizing, or plating. Iron and steel storage tanks having a wall thickness less than 6.4mm ( 1/4 (f) Each heating element must have a temperature regulating device. The device must limit the water from obtaining a temperature greater than 90 °C (194 °F). If the control has a marked off position, the control must disconnect the heating element from all ungrounded conductors, and it must not respond to temperature when placed in the off position. (g) An independent temperature limiting device must prevent the water in the upper 25 percent of the tank from attaining a temperature higher than 99 °C (210 °F). This device must require manual resetting, be trip free from the operating means, open all ungrounded power supply conductors to the heater, and be readily accessible. (h) Electric hot water supply boilers must have pressure and temperature relieving valves. The valve temperature setting must not be more than 99 °C (210 °F). The pressure relief setting must not be higher than the marked working pressure of the boiler. The pressure and temperature relief valves must meet subpart 53.05 of this subchapter. The pressure and temperature relief valves may be combined into a pressure-temperature relief valve. (i) Electric hot water supply boilers must be marked in a visible location with the manufacturer's name, model or other identification number, water capacity, and the electrical ratings of each heating element. When two or more heating elements are installed, the maximum wattage or current consumption must be indicated. The cold water inlet and the hot water outlet must each be clearly distinguished or marked for identification purposes. (j) All electric hot water supply boilers must have their pressure relief devices tested as required by part 52 or part 53 of this subchapter, as applicable. Electric hot water supply boilers that meet the requirements of UL 174 or UL 1453 and have heating elements, temperature regulating controls, and temperature limiting controls are satisfactory for installation and service without further installation testing. All electric hot water supply boilers not meeting the requirements of UL 174 or UL 1453 must have their heating elements, temperature regulating controls, and temperature limiting controls tested by the marine inspector at the time of installation. [CGD 88-057, 55 FR 24238, June 15, 1990, as amended by CGD 95-028, 62 FR 51202, Sept. 30, 1997; USCG-2003-16630, 73 FR 65191, Oct. 31, 2008; USCG-2020-0634, 89 FR 50198, June 12, 2024] § 63.25-5 Fired thermal fluid heaters. (a) Construction. (b) Controls. [CGD 88-057, 55 FR 24238, June 15, 1990, as amended by USCG-2020-0634, 89 FR 50198, June 12, 2024] § 63.25-7 Exhaust gas boilers. (a) Construction. (b) Controls. (c) Alarms. [CGD 88-057, 55 FR 24237, June 15, 1990, as amended by USCG-2020-0634, 89 FR 50198, June 12, 2024] § 63.25-9 Incinerators. (a) General. (2) An application for type approval of shipboard incinerators must be sent to the Commanding Officer, Marine Safety Center, U.S. Coast Guard, 2703 Martin Luther King Jr. Ave. SE, Washington, DC 20593, or it may be transmitted by email to the Commanding Officer (MSC), at [email protected] (b) Testing. (1) Have experienced and qualified personnel to conduct the inspections and tests required by this section; (2) Have documented proof of the qualifications to perform the inspections and tests required by this section; and (3) Not be owned or controlled by a manufacturer, supplier, or vendor of shipboard incinerators. (c) Prohibited substances. (1) Annex I, II, and III cargo residues of IMO MARPOL 73/78 (incorporated by reference; see § 63.05-1) and related contaminated packing materials. (2) Polychlorinated biphenyls (PCBs). (3) Garbage, as defined in Annex V of IMO MARPOL 73/78, containing more than traces of heavy metals. (4) Refined petroleum products containing halogen compounds. (d) Operating manual. (e) Training. (f) Acceptable methods and standards for testing emissions. (1) 40 CFR part 60 Appendix A, Method 1—Sample and velocity traverses for stationary sources; (2) 40 CFR part 60 Appendix A, Method 3A—Determination of oxygen and carbon dioxide concentrations in emissions from stationary sources (instrumental-analyzer procedure); (3) 40 CFR part 60 Appendix A, Method 5—Determination of particulate emissions from stationary sources; (4) 40 CFR part 60 Appendix A, Method 9—Visual determination of the opacity of emissions from stationary sources; (5) 40 CFR part 60 Appendix A, Method 10—Determination of carbon-monoxide emissions from stationary sources; (6) ISO 9096 (incorporated by reference; see § 63.05-1); and (7) ISO 10396 (incorporated by reference; see § 63.05-1). (g) Incinerators designed and tested to meet the requirements of IMO MEPC.244(66) (incorporated by reference; see § 63.05-1) are considered equivalent to the requirements of this section and may receive U.S. Coast Guard type approval. [USCG-2020-0634, 89 FR 50198, June 12, 2024]